Thorough examination and test - TExT - is the formal, COSHH-required health check that proves your kitchen extraction still controls fumes at source. Here is what it really involves.
LEV testing explained
Thorough examination and test - usually shortened to TExT - is the formal health check your local exhaust ventilation must pass to prove it is still controlling the fumes, grease and airborne contaminants it was installed to capture.
The phrase comes straight from the Control of Substances Hazardous to Health Regulations 2002. Regulation 9 says that where you rely on engineering controls such as extraction to protect people, those controls must be examined and tested thoroughly at suitable intervals - and the guidance that fleshes this out is the Health & Safety Executive's HSG258, Controlling airborne contaminants at work. It is easy to read "thorough examination and test" as a quick airflow reading and a certificate. It is not. Done properly, a TExT is a structured investigation into whether your system still does its job under real working conditions, and it produces a written verdict you can defend to an inspector, an insurer or a poorly employee's solicitor.
For a commercial kitchen this matters more than most people assume. Cooking fumes are a recognised health hazard, and the HSE's own catering guidance is explicit that the extraction system should be examined and tested at least once every 14 months. Below is what that examination actually looks like, step by step, and what each part is really telling you.
HSG258 breaks a TExT into three connected parts - a thorough examination, a measurement of technical performance, and an assessment of whether exposure is actually being controlled. In practice a competent examiner works through the following.
The reason HSG258 insists on all three parts is that each catches a failure the others miss. A canopy can pull a healthy face velocity while a grease-choked duct quietly strangles the system downstream; a fan can spin happily while contaminant spills sideways out of a badly positioned hood. Only by examining condition, measuring performance and testing control together can an examiner say, with evidence, that your kitchen extraction is still protecting people. That is the difference between a certificate and a genuine thorough examination and test.
Competence is central to the whole exercise. The regulations require the work to be done by a competent person, and the recognised route in the UK is BOHS training - the P601 qualification for LEV examination and testing. An examiner working to that standard knows how to interpret readings against commissioning data rather than simply confirming that air is moving. When you commission a TExT, it is reasonable to ask what qualification the examiner holds and to see it named on the report.
The output is a document, not just a visit, and it carries duties of its own. You must keep the report and make it available, and records should be retained for at least five years. It sits alongside your wider paperwork - the extraction TExT is one of the things an inspector expects to find, so it is worth understanding the documents an HSE inspector will ask for and keeping them together. The examination also feeds back into your risk paperwork, because the "adequately controlled" verdict only means anything against the exposures you identified when your COSHH assessment was actually done.
On timing, treat the 14-month figure carefully. It is a legal maximum for most systems, not a target, and HSG258 sets shorter intervals for certain higher-risk processes - some as frequent as monthly or six-monthly. For a busy kitchen, the practical driver is grease: heavy use loads filters and ducts quickly, so many operators examine and clean on a tighter cycle than the statutory ceiling. A TExT that comes back with a clean bill and a sensible interval is also your evidence that the routine cleaning and maintenance in between are keeping pace.
Thorough examination and test is not a formality bolted onto your cleaning contract. It is the regulated proof that your extraction still controls the fumes it was built to catch, and it only holds up when it is done thoroughly, by a competent person, and written down clearly.
Questions
For most LEV systems the legal maximum interval is 14 months, set by COSHH Regulation 9, and the HSE's catering guidance applies this to cooking-fume extraction. It is a ceiling, not a target - HSG258 requires shorter intervals for some higher-risk processes, and heavy kitchen use often justifies more frequent examination and cleaning. If in doubt, treat 14 months as the latest you should go, not the norm.
A quick airflow reading only tells you air is moving. A thorough examination and test has three parts - a physical examination of the whole system, measurement of its technical performance against commissioning data, and an assessment of whether exposure is genuinely being controlled. Only the full TExT produces the written verdict that satisfies COSHH and stands up to an inspector.
The work must be done by a competent person, and the recognised UK route is BOHS training such as the P601 qualification for LEV examination and testing. A competent examiner interprets your readings against the original commissioning figures rather than simply confirming airflow exists. It is reasonable to ask to see the examiner's qualification named on the report.
Phoenix Duct Clean · by the numbers