PhoenixDuctClean

What's measured

Face Velocity at a Fume Cupboard: What's Adequate?

For a ducted fume cupboard doing general work with hazardous substances, the accepted best-practice face velocity is around 0.5 metres per second at the sash, and if it drops below 0.45 the cupboard should come out of use until it is put right. The number on its own, though, no longer tells the whole story.

0.5 m/s
Best practice
500mm
Sash height
0.45 m/s
Out of use below
EN 14175
Standard
Containment
Now the focus
14 months
Test interval
0.5 m/sSASH
TR19 certificate Before & after photos Filters degreased Fully insured EHO accepted

The short answer

Around 0.5 m/s at the sash - but containment matters more

For a ducted fume cupboard doing general work with hazardous substances, the accepted best-practice face velocity is around 0.5 metres per second at the sash, and if it falls below 0.45 the cupboard should come out of use until it is put right. But airspeed alone no longer tells the whole story of whether a cupboard protects the person in front of it.

The detail

Where the number comes from

Face velocity is the speed of air drawn in through the open sash. The widely used benchmark is 0.5 m/s, plus or minus ten per cent, with the sash set to a 500 millimetre opening - the maximum safe opening marked on many cupboards is simply the aperture at which that velocity is reached. Below about 0.45 m/s the inward pull is treated as too weak to contain reliably, and older guidance noted that below roughly 0.3 m/s a cupboard is unlikely to be effective at all. Some higher-hazard work, such as certain radioactive materials, calls for a higher velocity again.

The British and European standard, BS EN 14175, is careful here: it does not actually set a required face velocity. What it specifies is that during type-testing and commissioning the velocity across an empty cupboard should not vary by more than about ten per cent from the average, and it puts the real emphasis on containment measured with tracer gas. Too much face velocity is its own problem - it creates turbulence around the operator and the sash that can pull contaminant back out rather than hold it in.

What it means for you

What a test actually checks

In practice a thorough examination checks the face velocity across a grid of points at the sash, confirms the readings do not vary excessively, and increasingly looks at containment rather than airspeed alone. Performance is judged against what the manufacturer confirmed at commissioning, which is why the commissioning figures matter as much as any generic benchmark.

A fume cupboard is examined and tested on the same fourteen-month cycle as other LEV under COSHH. A reading that has crept down since the last test, or that varies wildly across the sash, is a sign the extract, the make-up air or the cupboard itself has changed - and a cue to investigate before someone is exposed.

0.5 m/s
At 500mm sash
0.45 m/s
Out of use below
Containment
Now the focus

The service behind the guide

Fume cupboards tested to velocity and containment

We test fume cupboards to face velocity and containment against their commissioning performance, with a clear report and remedial actions where a unit falls short.

Questions

Frequently asked questions

What face velocity should a fume cupboard have?

Best practice for general hazardous work is around 0.5 m/s at a 500mm sash opening, within about ten per cent. Below 0.45 m/s the cupboard should be taken out of use until remedial work is done.

Does BS EN 14175 set a required face velocity?

No. The standard does not specify a required face velocity. It focuses on containment measured with tracer gas, and asks that velocity across an empty cupboard vary by no more than about ten per cent during type-testing and commissioning.

Can face velocity be too high?

Yes. Excessive face velocity creates turbulence around the sash and operator that can actually pull contaminant back out of the cupboard, so more is not always better.

How often must a fume cupboard be tested?

Like other LEV under COSHH, a fume cupboard must have a thorough examination and test at least every fourteen months by a competent person.

Why measure containment as well as velocity?

Face velocity alone does not prove a cupboard keeps fume off the operator. Tracer-gas containment testing measures what actually escapes at the sash, which is a more direct check of protection.

20+ Years of Experience

Phoenix Duct Clean · by the numbers

Kitchen canopies
degreased
4,287
Laundry ducts
cleaned
1,877
LEV systems
tested
1,658
Hours
on site
54,754

Need your fume cupboards tested to standard?

We test fume cupboards to face velocity and containment against their commissioning performance, on the fourteen-month cycle, with a clear report and remedial actions.